Aluminium Entrance Conductor

< Back

AMP Size Wire Size Neutral Insulated Conduit Copper Clad Ground Wire Ground Rod
60 #4 #4 1 1/4" #6 5/8" x 8'
100 #2 #4 1 1/4" #6 5/8" x 8'
200 #4/0 #2/0 2" #4 5/8" x 8'
320 #500 MCM or #4/0 to (2) 200A panels #350 MCM or #2/0 to (2) 200A panels 3" #2
or (2) #4 to single rod
5/8" x 8'